What it does
Converts thermocouple voltage (mV) to temperature, or temperature to voltage, for types K, J, T and E using the NIST ITS-90 reference functions. Optional cold junction compensation.
How to use
- Choose the conversion mode and thermocouple type.
- Enter the measured voltage (mV) or the temperature, depending on the mode.
- Pick the temperature unit (°C, °F, K).
- Enter the cold junction (meter terminal) temperature, or leave blank for 0 °C.
- Temperature → EMF:
E(t) = Σ cᵢ·tⁱ (NIST polynomial, t in °C). Type K above 0 °C adds a₀·exp(a₁·(t − a₂)²).
- Cold junction compensation:
E_total = E_measured + E(T_cj).
- mV → temperature: solves
E(t) = E_total numerically with the same polynomials.
- Voltage at meter for a known hot-junction temperature:
E(T_hot) − E(T_cj).
Valid ranges
| Type |
Range (°C) |
| K |
−270 to 1372 |
| J |
−210 to 1200 |
| T |
−270 to 400 |
| E |
−270 to 1000 |
FAQ
Why does my reading differ from the meter? Meters apply their own cold junction compensation; enter the meter terminal temperature to match.
Does it include sensor tolerance? No. Results are for an ideal thermocouple; real wire has tolerance (e.g. ±1.5 °C or ±0.4 % for Class 1/2 type K).
Out of range error? The voltage or temperature is outside the NIST range for the selected type.